Potential Power Highest Inverter

This signal calculates potential power based on the highest yield for any reference inverter of this inverter.

Technology

Solar

Remarks

The reference inverters used will be all inverters configured as references for this inverter. If no reference inverters are configured, all other inverters in the same site will be used instead.

Required metadata fields:

  • DC Capacity (kWp) (Inverter metadata 7)

Optional metadata fields:

  • Availability Irradiance Cut-In (W/m2) (Inverter metadata 8)

Equation
Potential_Power_Highest_Inverter_-_Equation.png

Where:

Pp

is the Potential power (highest inverter)

Cut-inIA

is the Availability Irradiance Cut-In (W/m2) (Inverter metadata 8)

I

is the Solar Irradiance Reference for each time step

CDC

is the DC capacity (kWp) (Inverter metadata 7)

Iref

the set of references inverters for this inverter

Yi

is the Yield DC value for inverter i

Inputs
Potential_Power_Highest_Inverter_-_Inputs.png
Usage Example

In this example, Esperta 1 has references to both of the other 2 and in the marked datapoint, the Yield DC of Soleadia 1 has a peak. This makes the Potential power (highest inverter) of Esperta 1 also peak over Esperta 2, which has no reference inverters and takes the highest value from the site inverters instead.

Potential_Power_Highest_Inverter_-_Usage_Example.png